The Joule Smartherm Multi-Energy commercial range of cylinders are engineered with multiple connectios to allow different heat sources and heat stratification in the system. This allows the system to be a perfect partner for solar, Heat Pumps, Pellet Burners, Heat Recovery Systems, District Heating and much more.

Categories: SmarTherm

General
  Item Code
6bar. TCFMVDX0300LFD TCFMVDX0400LFD TCFMVDX0500LFD TCFMVDX0800LFD TCFMVDX1000LFD
Multi Energy 300 400 500 800 1000
Titanium Imm. – Fact. Fitted As Std. 3 x 6kW 3 x 6kW 3 x 6kW 3 x 6kW 2 x 6kW
No. Of Imm Heater Bosses In Total 4x Screw 3x Screw + 1x Flange
Maximum Energy Input Permitted (kW) 48 48 48 48 78
Inspection Flange Optional – CANNOT be used for flanged imm. heaters Supplied as std – CAN be used for fl. imm.
Heat Up Time ΔT 50°C Reheat time in mins = Litres x 3.2 / kW installed

 

All Cylinders – 3 & 6 bar 300 400 500 800 1000
Diameter (mm) 620 710 710 920 1100
Height (mm) 1670 1670 2030 2050 2170
Hot And Cold Connections BSP F 1.5” 1.5” 1.5” 2.0” 2.0”
Coil Conn. (+for the solar coil) BSP F 1.5” 1.5” 1.5” 1.5” 1.5”
Secondary Return BSP F 1.25” 1.25” 1.25” 1.25” 1.25”
Max. Op. Pressure – 3/6 bar kit (bar) 6 / 10 6 / 10 6 / 10 6 / 10 6 / 10
T&P Setting 3/6 bar kit (bar) 7 / 10 7 / 10 7 / 10 7 / 10 7 / 10
T&P Size – Multi Energy / Indirect+Solar 1.0” / 0.75” 1.0” / 0.75” 1.0” / 0.75” 1.0” / 0.75” 1.25” / 0.75”
Cold W. Safety Devices – PRV, ERV, Chk Vlv 1.0” (one piece) 1.25” (multi-piece)
Exp. Relief Valve Setting – 3/6 bar kit (bar) 6 / 8 6 / 8 6 / 8 6 / 8 6 / 8
2-port Mot. Valve (Indirect & Solar Only) 28mm 28mm 28mm 28mm 1.25”
2-port Mot. Valve Conn. (Ind & Sol Only) Compression nut and olive Pipe union conn. nut and tail piece
Expansion Vessel Size – 3/6 bar kit (ltr) 24 / 35 35 / 50 50 / 80 80 / 100 100 / 150
Tundish 1.25” 1.25” 1.25” 1.25” 1.5”
ErP Energy Efficiency Class C C C C C
Standing Loss (W) 92 102 115 121 124

 

Performance 300 400 500 800 1000
Hot Water Capacity (ltr) 289.5 391 497 766 1097
Quantity Of Factory Fitted Immersions 3 3 3 3 2
Rating Of Factory Fitted Imm. (kW/V) 6/240 6/240 6/240 6/240 6/240
Factory Fitted Immersion Type Titanium
Number Of Immersion Bosses 4 4 4 4 2
Max. Allowable Power Outp. Of Imm. (kW) 48 48 48 48 78
Inspection Flange Optional Standard
Heat Up Time (ΔT 50°C) min 53 71 89 143 *
Fact. Fitted kW 18 18 18 18 12
Cont. Output – Fact. Fitted L/hr 281 281 281 281 *
Heat Up Time (ΔT 50°C) min 21 29 37 57 49
Max. Allowed kW 48 48 48 48 78
Cont. Output @60ºC – Max. Allowed L/hr 826 826 826 826 1342
Weight Empty (kg) 71.5 72 89 186 188
Weight Full (kg) 361 463 586 952 1285