Outdoor Unit |
HHSM-G600005-1 |
HHSM-G600008-1 |
HHSM-G600012-1 |
HHSM-G600016-1 |
||||
System | Operation | Nominal Capacity | Heating
A7/W351/A7/W552 |
W |
5.000/4.300 |
8.000/7.100 |
12.000/11.300 |
16.000/15.000 |
Cooling
A35/W181 |
W |
5.000 |
7.500 |
12.000 |
14.000 |
|||
Power Input
(Nominal) |
Heating
A7/W351/A7/W552 |
W |
1.030/1.520 |
1.770/2.530 |
2.650/3.730 |
3.620/5.180 |
||
Cooling A35/W181 | W |
1.140 |
1.900 |
2.770 |
3.280 |
|||
COP (Nominal Heating) A7/W351/A7/W552 | W/W |
4,85/2,83 |
4,52/2,81 |
4,53/3,03 |
4,42/2,90 |
|||
EER (Nominal Cooling) A35/W181 | W/W |
4,39 |
3,95 |
4,33 |
4,27 |
|||
SCOP LWT 350c/550c | W/W |
4,46/3,2 |
4,44/3,23 |
4,69/3,51 |
4,48/3,53 |
|||
Average Seasonal Space Heating Eff.Class* | – |
A+++/A++ |
A+++/A++ |
A+++/A++ |
A+++/A++ |
|||
Current | MCA | A |
16,00 |
22,00 |
28,00 |
32,00 |
||
MFA | A |
20,00 |
27,50 |
35,00 |
40,00 |
|||
Water Flow Rate | Min | L/MIN |
7,00 |
7,00 |
12,00 |
12,00 |
||
Max | L/MIN |
48,00 |
48,00 |
58,00 |
58,00 |
|||
Leaving Water Temp | Heating | 0C |
15-65 |
15-65 |
15-65 |
15-65 |
||
Cooling | 0C |
5-25 |
5-25 |
5-25 |
5-25 |
|||
Function | Smart Grid Ready | – | Yes | Yes | Yes | Yes | ||
PV Enabled | – | Yes | Yes | Yes | Yes | |||
2-Zone Control | – | Yes | Yes | Yes | Yes | |||
Indoor Compact
Unit |
Power Supply | 0,#,V,Hz |
220-240V, 50Hz, 1 |
220-240V, 50Hz, 1 |
220-240V, 50Hz, 1 |
220-240V, 50Hz, 1 |
||
Water Tank Volume | Litres |
180/230 |
180/230 |
180/230 |
180/230 |
|||
Declared Load Profile | L/XL | |||||||
Energy Efficiency Classes | – |
A |
A |
A |
A |
|||
Sound | Sound Pressure | Heating/
Cooling Std |
dB(A) | |||||
Sound Power | Heating Std | dB(A) | ||||||
Dimensions | Net Weight | KG |
85/90 |
85/90 |
85/90 |
85/90 |
||
Net Dimensions
(WxHxD) |
MM |
1900 x 595 x 625 |
1900 x 595 x 625 |
1900 x 595 x 625 |
1900 x 595 x 625 |
|||
Outdoor Unit | Power Supply |
0,#,V,Hz |
10,220-240V,50Hz |
10,220-240V,50Hz |
10,220-240V,50Hz |
10,220-240V,50Hz |
||
Compressor | Type | – |
BLDC Twin Rotary |
BLDC Twin Rotary |
BLDC Twin Rotary |
BLDC Twin Rotary |
||
Base Heater | – | — | Yes | Yes | Yes | |||
Sound | Sound |
Heating Std |
dB(A) |
45 | 48 | 50 | 52 | |
Pressure |
Cooling Std |
dB(A) |
45 | 48 | 50 | 54 | ||
Sound |
Heating Std |
dB(A) |
61 | 63 | 64 | 66 | ||
Power |
Cooling Std |
dB(A) |
62 | 64 | 65 | 68 | ||
Dimensions | Net Weight | KG | 58.5 | 76 | 110 | 110 | ||
Net Dimensions (WxHxD) |
MM |
880 x 798 x 310 |
940 x 998 x 330 |
940 x 1420 x 330 |
940 x 1420 x 330 |
|||
Refrigerant |
Type |
– |
R32 |
R32 |
R32 |
R32 |
||
Factory Charging |
tC02e |
0,68 |
0,78 |
1,49 |
1,49 |
|||
KG |
1,00 |
1,15 |
2,20 |
2,20 |
||||
Piping |
Water Pipe |
Inlet/Outlet |
0,mm |
28/28 |
28/28 |
28/28 |
28/28 |
|
Water Pipe (DHW) |
Inlet/Outlet |
0,mm |
22/22 |
22/22 |
22/22 |
22/22 |
||
Ambient Temperature |
Heating |
0C |
-25-35 |
-25-35 |
-25-35 |
-25-35 |
||
Cooling |
0C |
10-46 |
10-46 |
10-46 |
10-46 |
|||
DHW |
0C |
-25-43 |
-25-43 |
-25-43 |
-25-43 |
8KW R32 Air Source Heat Pump
Features & Benefits
A Joule Samsung heat pump is an energy-efficient system that uses the heat from the ambient air for heating and hot water. By using the ambient air and transferring this heat into the house through a hydronic system, such as underfloor heating, a heat pump requires less power input and offers greater power output than conventional boilers.
Solution Key Features
- 7-year Warranty
- SCOP: Best on MCS Database – 4.85
- 65°C Hot Water
- 45dB(A) – Quietest System on the Market
- 5Kw Outputs
- Low GWP Refrigerant – R32
Categories:
General
Videos
Downloads
Setting Out
Electrical
Mechanical
SPARE PARTS